Mechanical Response Analysis of Cross Line Downlead Conductor Structure System in Substation
-
摘要: 以某750 kV变电站工程为背景,利用三点受弯试验测扩径铝绞线JLHN58K-1600抗弯刚度值,并建立了变电站跨线-引下线结构体系有限元模型,针对考虑抗弯刚度影响的导线刚度模型进行了多工况、多参数影响下的力学响应分析。结果表明:导线受力对结构跨度和布置方式较敏感,结构跨度越大、两端高差越大,导线的张力显著上升,且对于跨线而言,30 m跨线跨度为明显转折点,超过该跨度后,跨线水平张力增幅更为明显;引下线布置形式会影响结构受力承担效果,相较于一字形引下线,人字形引下线因具备水平方向的附加约束能力,能更有效减小横向偏移与振动,减小导线张力;组合使用一字形与人字形引下线能进一步分散荷载,使导线张力达到最小值。
-
关键词:
- 变电站跨线-引下线结构 /
- 数值模拟 /
- 力学性能 /
- 抗弯刚度 /
- 试验研究
Abstract: This study investigates a 750 kV substation project, focusing on the mechanical behavior of expanded aluminum stranded conductors (JLHN58K-1600). The flexural rigidity of the conductors was obtained through three-point bending tests. A finite element model of the substation’s overhead-downlead conductor system was established to analyze the mechanical responses of conductor stiffness models considering flexural rigidity under multiple working conditions and parametric variations. The analysis results indicate that the mechanical performance of the conductors is highly sensitive to structural span and layout configuration. As the span and the height difference between the two ends increase, conductor tension increases significantly. Notably, for overhead conductors, a span of 30 meters conductors serves as a critical threshold, beyond which the increase in horizontal tension becomes more pronounced. The layout of downlead conductors also influences the load-bearing behavior of the structure. Compared with single-vertical (straight-line) configurations, V-shaped (inverted-V) downleads provide additional horizontal constraints, effectively reducing lateral displacement and vibration, and consequently decreasing conductor tension. A combined use of straight-line and V-shaped downleads further distributes the load, minimizing overall conductor tension. -
[1] 陈景彦,陈建华,毕春丽,等. 大截面导线的力学计算与实验研究[J]. 电力建设,2004(9):44-45. [2] 晏致涛,黄静文,李正良. 基于结点6自由度的分裂导线有限元模型[J]. 工程力学,2012,29(8):325-332. [3] 彭波,赵彬,刘彬,等. 一种基于超长弹性细杆模型的大截面导线弧垂计算方法[J]. 电测与仪表,2018,55(4):70-73. [4] 何畅,谢强,杨振宇,等. 变电站分裂导线弯曲性能研究[J]. 中国电机工程学报,2018,38(15):4585-4592. [5] 丁翰林. 典型导线的拉弯耦合力学性能和垂度影响研究[D]. 重庆:重庆科技学院,2023. [6] 李清,马伦,解健,等. 大档距多分裂输电导线扭转刚度计算分析[J]. 高压电器,2020,56(2):158-162. [7] 余国庆. 强风环境下变电站引下线结构风振响应分析[D]. 重庆:重庆大学,2020. [8] 余国庆,晏致涛,王欣欣,等. 变电站引下线体系时域非线性风振分析[J]. 重庆大学学报,2023,46(10):107-117. [9] 郭栋才. 高压变电站引下线及连接金具系统力学性能研究[D]. 太原:太原理工大学,2023. [10] 陈亦,祝益民. 架空线抗弯刚度及其计算方法探析[J]. 机电信息,2014(33):94-95. [11] 中国电力工程顾问集团有限公司,中国能源建设集团规划设计有限公司. 电力工程设计手册,第23分册变电站设计[M]. 北京:中国电力出版社,2019. -
点击查看大图
计量
- 文章访问数: 18
- HTML全文浏览量: 7
- PDF下载量: 0
- 被引次数: 0
登录
注册
E-alert
登录
注册
E-alert
下载: