Source Journal of Chinese Scientific and Technical Papers
Included as T2 Level in the High-Quality Science and Technology Journals in the Field of Architectural Science
Core Journal of RCCSE
Included in the CAS Content Collection
Included in the JST China
Indexed in World Journal Clout Index (WJCI) Report
Volume 56 Issue 10
Oct.  2026
Turn off MathJax
Article Contents
WANG Fen, ZHANG Dajian, LI Yongxing, MIAO Pengyong, WANG Wenrui. Spatiotemporal Monitoring and Analysis of Hydration Heat in Ultra-Long Water Treatment Tank Slabs Based on Densely Distributed UWFBG-Finite Element Coupling[J]. INDUSTRIAL CONSTRUCTION, 2026, 56(10): 132-144. doi: 10.3724/j.gyjzG26012804
Citation: WANG Fen, ZHANG Dajian, LI Yongxing, MIAO Pengyong, WANG Wenrui. Spatiotemporal Monitoring and Analysis of Hydration Heat in Ultra-Long Water Treatment Tank Slabs Based on Densely Distributed UWFBG-Finite Element Coupling[J]. INDUSTRIAL CONSTRUCTION, 2026, 56(10): 132-144. doi: 10.3724/j.gyjzG26012804

Spatiotemporal Monitoring and Analysis of Hydration Heat in Ultra-Long Water Treatment Tank Slabs Based on Densely Distributed UWFBG-Finite Element Coupling

doi: 10.3724/j.gyjzG26012804
  • Received Date: 2026-01-28
    Available Online: 2026-11-06
  • To address the early-age cracking issue of the ultra-long base slab in coal mine water treatment tanks caused by hydration heat accumulation and structural constraints, this study integrated densely distributed ultra-weak fiber Bragg grating (UWFBG) sensing with ABAQUS finite element simulation. This approach was used to conduct spatiotemporal monitoring and analysis of hydration heat and strain in a 106.6 m long, 500 mm thick C40 concrete base slab. Distributed temperature sensing (DTS) and distributed strain sensing (DSS) optical cables were deployed in the top and bottom protective layers of the base slab, enabling monitoring at a spatial resolution of 1 m and a sampling interval of 10 min. A coupled hydration heat-shrinkage model was established using the HETVAL subroutine, the FILM subroutine, and a shrinkage subroutine. The results showed that the peak temperature of the lower protective layer ranged from 54.90 to 59.90 ℃, which was higher than the range of 46.9 to 51.58 ℃ observed in the upper protective layer, with a maximum temperature difference of 8 ℃. The rebar strain exhibited a three-stage characteristic: tensile strain of (170-190)×10-6 during the heating phase, transition to compressive strain during the cooling phase, and stabilization from -46×10-6 to -62×10-6 after 200 hours. The errors for both temperature and strain indicators are kept within 8%. The maximum principal tensile strain of concrete (38-42)×10-6 was lower than the 7-day allowable value of 46×10-6. Due to the implementation of post-pour strip measures, no risk of early-age cracking was observed.
  • loading
  • [1]
    王星星,赖庆文,廖光明,等.岩石地基超长水池结构不设缝设计要点[J].特种结构,2023,40(3):42-46.
    [2]
    吴彬,杨浩文,纪宪坤,等.超长圆形水池温度作用分析与计算[J].特种结构,2025,42(2):93-97.
    [3]
    李喜强,张珂,朱国军,等.污水处理池超长结构混凝土裂缝控制技术研究[J].建材世界,2025,46(1):40-43.
    [4]
    张轩旗,何华飞,张仲宇,等.地下结构大体积混凝土水化热效应及温控措施[J].市政技术,2025,43(6):43-51.
    [5]
    刘羽翼,刘孟富,吕义辉,等.沙漠重载铁路槽型梁水化热温度监测与分析[J].中国测试,2025,51(6):97-105.
    [6]
    CAI Y,GAO S,WANG F,et al. Early hydration heat temperature field of precast concrete T-beam under steam curing:Experiment and simulation[J]. Case Studies in Construction Materials,2023,18:e02067.
    [7]
    耿鸣山,林尔姬,吕建兵,等.大体积混凝土承台的水化热分析及温控研究[J].混凝土,2021(9):50-55.
    [8]
    王博.大体积混凝土承台水化热效应及温控措施研究[D].西安:长安大学,2019.
    [9]
    朱伯芳,吴龙珅,张国新,等.混凝土坝初期水管冷却方式研究[J].水力发电,2010,36(3):31-35.
    [10]
    胡双达.大体积混凝土主动控温技术研究[D].北京:交通运输部公路科学研究所,2017.
    [11]
    XU K,WANG F,WANG Y,et al. Large-capacity interrogation for ultra-weak fiber Bragg grating array with a DFB Laser Array Chip[J]. Journal of Lightwave Technology,2025,43(17):8467-8473.
    [12]
    LIU K,WANG X,LUO Z. Pre-tension-free distributed UW-FBG detection method for two-dimensional bearing capacity of super-long bored piles[J]. Journal of Modern Optics,2025,72(10/11/12):382-390.
    [13]
    ZHANG H,SU C,CHEN X,et al. Calculation of mass concrete temperature and creep stress under the influence of local air heat transfer[J]. Computer Modeling in Engineering & Sciences,2024,140(3):2977.
    [14]
    HABRAH A,ABU-TAIR A I. The reliability of the ACI 209R-92 method in predicting column shortening in high-rise concrete buildings[C]//International Sustainable Buildings Symposium. Cham:Springer International Publishing,2017:396-412.
    [15]
    PAN Z,ZHANG H,ZENG B,et al. Statistical evaluation of CEB-FIP 2010 model for concrete creep and shrinkage[J]. Materials,2023,16(4):1576.
    [16]
    BAŽANT Z P,BAWEJA S. Creep and shrinkage prediction model for analysis and design of concrete structures:Model B3[J]. ACI Special Publications,2000,194:1-84.
    [17]
    中华人民共和国住房和城乡建设部.混凝土结构设计标准:GB/T 50010-2010[S].北京:中国建筑工业出版社,2024.
    [18]
    孙绕忠,高鹏,朱文兵,等.基于ABAQUS的混凝土温度场模拟方法[J].工程与建设,2021,35(6):1359-1361.
    [19]
    王彦磊,朱劲松.基于混凝土徐变及收缩智能预测的预应力钢筋混凝土桥梁长期变形分析方法[J].中国公路学报,2025,38(11):51-63.
    [20]
    刘毅强,刘松,谌超,等.散热系数及水泥用量对混凝土温度及应力的影响研究[J].施工技术,2015,44(24):45-47.
  • 加载中

Catalog

    通讯作者: 陈斌, bchen63@163.com
    • 1. 

      沈阳化工大学材料科学与工程学院 沈阳 110142

    1. 本站搜索
    2. 百度学术搜索
    3. 万方数据库搜索
    4. CNKI搜索

    Article Metrics

    Article views (27) PDF downloads(0) Cited by()
    Proportional views
    Related

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return