Turn off MathJax
Article Contents
WANG Zhiyuan, HU Zujun, LI Sheng, LI Suchao, LIU Zhenliang. SHAKING TABLE TESTS OF VERTICAL ISOLATION FOR TRANSFORMER MODELS BASED ON METALLIC RUBBER CUSHION AND SPRINGS[J]. INDUSTRIAL CONSTRUCTION, 2021, 51(11): 7-12. doi: 10.13204/j.gyjzG21052420
Citation: WANG Zhiyuan, HU Zujun, LI Sheng, LI Suchao, LIU Zhenliang. SHAKING TABLE TESTS OF VERTICAL ISOLATION FOR TRANSFORMER MODELS BASED ON METALLIC RUBBER CUSHION AND SPRINGS[J]. INDUSTRIAL CONSTRUCTION, 2021, 51(11): 7-12. doi: 10.13204/j.gyjzG21052420

SHAKING TABLE TESTS OF VERTICAL ISOLATION FOR TRANSFORMER MODELS BASED ON METALLIC RUBBER CUSHION AND SPRINGS

doi: 10.13204/j.gyjzG21052420
  • Received Date: 2021-05-24
    Available Online: 2022-03-29
  • In order to study the influence of wire diameters and nominal densities on the mechanical properties of metallic rubber(MR) cushions in different parameters and preloading conditions, and to verify whether the mechanical properties of metallic rubber cushious stable in preloading conditions, a three-dimensional(3 D) isolation device was proposed based on metallic rubber cushions and springs. Then, vertical isolation shaking table tests were conducted on a scaled isolated transformer model, and the dynamic characteristics of the isolated structure, as well as the vertical acceleration response of the structure under unidirectional or bidirectional input were measured. The results showed that the mechanical properties of metallic rubber under preloading were stable, and the vertical isolation device based on metallic rubber cushions and springs could effectively reduce the natural frequencies of structures and effectively reduce the energy input, and the isolation efficiency increased with the increment of the peak ground acceleration.
  • loading
  • [1]
    中华人民共和国国家标准.电力设施抗震设计规范:GB 50260-2013[S].北京:中国计划出版社,2013.
    [2]
    张琪.交流特高压变电站主要电气设备抗震措施效果及现场应用研究[D].济南:山东大学,2020.
    [3]
    MUROTA N,FENG M Q,LIU G Y.Earthquake Simulator Testing of Base-Isolated Power Transformers[J].IEEE Transactions on Power Delivery,2006,21(3):1291-1299.
    [4]
    GÖKÇE T,YÜKSEL E O.Seismic Performance Enhancement of High-Voltage Post Insulators by a Polyurethane Spring Isolation Device[J].Bulletin of Earthquake Engineering:Official Publication of the European Association for Earthquake Enginee-ring,2019,17(3):1739-1762.
    [5]
    日本电气技术标准调查委员会.电气设备抗震设计指南:JEAG 5003-1980[S].周书瑞,郭展潮,译.北京:技术标准出版社,1984.
    [6]
    马国梁,谢强.大型变压器的基础隔震摩擦摆系统理论研究[J].中国电机工程学报,2017,37(3):946-955.
    [7]
    熊明攀.基于不同地震动参数的变电站高压电气设备易损性研究[D].北京:中国地震局工程力学研究所,2016.
    [8]
    LEE D,CONSTANTINOU M C.Combined Horizontal-Vertical Seismic Isolation System for High-Voltage-Power Transformers:Development,Testing and Validation[J].Bulletin of Earthquake Engineering,2018,16(2):4273-4296.
    [9]
    邓长根,曾苗,徐忠根.结构工程竖向隔震技术研究进展[J].建筑科学与工程学报,2019,36(4):1-11.
    [10]
    张大义,夏颖,张启成.金属橡胶力学性能研究进展与展望[J].航空动力学报,2018,33(6):161-174.
    [11]
    王亚杰,赵亚哥白,任小龙.金属橡胶的本构关系研究[J].山西建筑,2019,45(4):29-31.
    [12]
    李素超.形状记忆合金橡胶力学行为及桥梁碰撞减震研究[D].哈尔滨:哈尔滨工业大学,2012.