Experimental Research on Weathering Steel Deviation Angle Towers Under Static Loads
-
摘要: 为了验证耐候冷弯型钢应用于转角塔的安全性,以安徽某设计有限公司设计的220 kV电压等级的SJ2-18型转角塔为例,展开耐候冷弯型钢转角塔真型试验研究。采用耐候冷弯型钢制造的SJ2-18型转角塔通过了8个工况的100%设计载荷测试,当荷载达到140%时,转角塔支腿与塔脚连接螺栓发生剪切破坏。结果表明:SJ2-18型转角塔结构设计合理,强度安全可靠,能够满足DL/T 5154—2012《架空输电线路杆塔结构设计技术规定》的要求。研究结论为耐候冷弯型钢在转角塔中的应用提供了试验依据,对耐候冷弯型钢转角塔的推广提供了技术支持。Abstract: Taking a SJ2-18 deviation angle tower with 220 kV voltage level designed by a design company in Anhui as an example, the research on full-scale test of the tower was carried out to verify the safety of weather-resistant cold-formed steel applied to deviation angle towers. The SJ2-18 deviation angle tower made of weather-resistant cold-formed steel passed the 100% design load test under 8 working conditions. The shear failure of the connecting bolts between the SJ2-18 leg and the SJ2-18 foot occurred when the load reached 140%. The test results showed that the structure design of the SJ2-18 deviation angle tower was reasonable, with safe and reliable strength which could meet the requirements of DL/T 5154-2012. The research results could provide an experimental basis for the application of weather-resistant cold-formed steel deviation angle towers, and provide technical support for the promotion of weather-resistant cold-formed steel deviation angle towers.
-
Key words:
- deviation angle tower /
- full-scale test /
- weathering and cold-formed steel /
- displacement /
- strain
-
[1] 陈城,许海源,王晨,等.500 kV输电塔线体系强风荷载倒塌分析[J].工业建筑,2019,49(12):36-41. [2] 王凌旭,姚瑶,张有佳,等.不同覆冰状态下输电塔线体系脱冰及断线受力分析[J].工业建筑,2019,49(12):7-12. [3] TIAN L,FU Z Y,PAN H Y,et al.Experimental and numerical study on the collapse failure of long-span transmission tower-line systems subjected to extremely severe earthquakes[J].Earthquake and Structures,2019,16(5):513-522. [4] YANG F L,HAN J K,YANG J B,et al.Study on the application of weathering and cold-formed steel in transmission tower[C]//2009 Asia-Pacific Power and Energy Engineering Conference.2019:1-4. [5] 杨风利,韩军科,杨靖波,等.输电铁塔用耐候钢节点耐腐蚀性能试验研究[J].电力建设,2008(9):23-28. [6] 李正,冯卫民,赵金飞,等.耐候冷弯型钢在220 kV输电线路中的应用[J].电力建设,2010,31(7):101-104. [7] 韩军科,杨风利,赵金飞,等.耐候冷弯型钢输电铁塔真型试验研究[J].工业建筑,2016,46(8):1-6. [8] YAO Y,WANG L X,ZHANG Y J.Stability and reinforcement analysis of weathering steel high voltage transmission tower[C]//IOP.Materials Science and Engineering.2019:1-8. [9] 中华人民共和国住房和城乡建设部.110 kV-750 kV架空输电线路设计规范:GB 50545-2010[S].北京:中国计划出版社,2010. [10] 中华人民共和国国家能源局.架空输电线路杆塔结构设计技术规定:DL/T 5154-2012[S].北京:中国计划出版社,2012. [11] 中华人民共和国住房和城乡建设部.钢结构设计标准:GB 50017-2017[S].北京:中国建筑工业出版社,2018. [12] 中华人民共和国建设部.冷弯薄壁型钢结构技术规范:GB 50018-2002[S].北京:中国计划出版社,2002.
点击查看大图
计量
- 文章访问数: 98
- HTML全文浏览量: 11
- PDF下载量: 1
- 被引次数: 0