APPLICATION OF PRESTRESSED JOIST BEAMS FOR REMOVING COLUMN IN REFORM OF BUILDINGS
-
摘要: 青岛奥帆基地西地块商业中心,地下2层,地上3层(局部4层),框架结构。由于商业布局改变,需拆除1~2层共6个框架柱,拆除后框架梁跨度18m。采用有粘结预应力加固原有框架梁,取得较好效果。可供类似工程的加固设计参考。Abstract: Six columns on the first and second floors of a commercial building in Qingdao are required to be removed for functional purpose. The structural form of the building is RC frame,having 2 stories in the basement and 3 stories above the ground (4 stories partially) . Due to the columns removed,the span of the corresponding beam is increased to 18 meters. Bonded prestress technique is used to strengthen the original frame beam in order to sustain the increased loads,good result is obtained. The method used in this project can be referred by the reinforcing design of similar projects.
-
Key words:
- column removed /
- bonded prestress /
- frame
-
T. Y. Lin,Burns N H. 预应力混凝土结构设计[M]. 路湛沁,译. 北京:中国铁道出版社,1983. [2] GB 500112001 建筑抗震设计规范[S]. [3] GB 500102002 混凝土结构设计规范[S]. [4] GB 503672006 混凝土结构加固设计规范[S]. [5] JGJ 1452004,J 4072005 混凝土结构后锚固技术规程[S]. [6] 张开臣,王丰,司波,等. 加固改造工程中旧柱新梁设计和施工[J]. 工业建筑,2009,39(11) : 126-128. 期刊类型引用(5)
1. 牟浩娜,尹新生. 无粘结预应力混凝土结构抗震性能研究分析. 建筑技术. 2024(14): 1772-1776 . 百度学术
2. 田宝龙,赵腾飞. 装配式混凝土框架节点抗震性能研究进展. 低温建筑技术. 2024(06): 118-122 . 百度学术
3. 阎石,杜若鸣,赵子豪. 自复位梁-柱节点的耗能与复位能力协调关系研究. 沈阳建筑大学学报(自然科学版). 2024(05): 789-796 . 百度学术
4. 范夕森,张子健,刘琪,李莹. 角钢连接的装配式混凝土梁柱节点塑性阶段力学性能研究. 四川建筑科学研究. 2022(04): 1-9 . 百度学术
5. 赵飞. 预应力混凝土梁与型钢混凝土柱中节点受剪性能研究. 建筑科技. 2022(05): 34-40 . 百度学术
其他类型引用(7)
-

计量
- 文章访问数: 110
- HTML全文浏览量: 6
- PDF下载量: 121
- 被引次数: 12